Installation covers the work on site: a safety plan and hazard controls, raceways, electrical equipment, DC and AC conductors, grounding and bonding, the utility interconnection, monitoring hardware, batteries, ground and building mounts, and the modules. Safety tasks in this domain draw on OSHA's construction rules in 29 CFR 1926 and on NFPA 70E for electrical hazards, both on NABCEP's reference list.
Code sections to know by number
- 690.7 to 690.9: maximum voltage, circuit current and overcurrent protection.
- 690.12: rapid shutdown of PV systems on buildings. The section sets a voltage and a time limit for conductors outside the array boundary and separate requirements inside it; learn both as the 2017 text states them, since later editions reworked the inside-array options.
- 690.13 and 690.15: the PV system disconnect and the disconnects that isolate equipment.
- 690.31: wiring methods. 690.41 to 690.47: system grounding, equipment grounding and the electrode.
- 690.53 to 690.56: marking and labels.
- 705.12: the point of connection, with supply-side connections in 705.12(A) and load-side connections in 705.12(B). The 2014 code had the load side in 705.12(D), and the 2020 code moved the supply side to a new 705.11, so older and newer study material cites different numbers.
- Article 706 for energy storage systems, new in 2017, and Article 480 for storage batteries.
- 310.15: ampacity, with the correction and adjustment tables and, in 310.15(B)(3)(c), a separate temperature rule for raceways and cables in sunlight on rooftops.
Conductor ampacity under conditions of use
A conductor's table ampacity is reduced for the ambient temperature it runs in and again for the number of current-carrying conductors sharing the raceway:
Iallowed = Itable × ktemp × kfill
The result has to cover the current found under 690.8; check the termination temperature rating as well, because the smaller value governs.
Inverter output and the load-side connection
The inverter output circuit uses the same continuous-duty factor: 125 percent of the inverter's rated output current, rounded up to the next standard breaker size. Where that breaker lands on a panel's busbar, 705.12(B)(2) limits how much current the busbar may see from all sources. One of the options in 705.12(B)(2)(3), which carries conditions of its own, lets the sum of 125 percent of the inverter output current and the main breaker rating reach 120 percent of the busbar rating:
1.25 × Iinv + Imain ≤ 1.2 × Ibus
The 2017 text sets out each option with its conditions; read them all before applying any one of them.
Voltage drop
The code treats voltage drop as a design recommendation rather than a hard limit, but it is a standard calculation for a long DC run. For a two-wire circuit of one-way length L in feet, current I and conductor resistance R in ohms per 1,000 ft:
Vdrop = 2 × L × I × R / 1,000
% drop = Vdrop / V × 100